Advantech BB-MESP211 Serie

SPHINX in Europa
CH
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Produktgruppen > Gateways > Advantech BB-MESP211 Serie

Advantech BB-MESP211 Serie

Ultra Compact Modbus Gateways

Advantech BB-MESP211 Serie
5824_18160.jpg
  • EigenschaftenEigenschaften
  • BeschreibungBeschreibung
  • Weitere InformationenWeitere Informationen
  • PDFPDF
  • Modbus TCP Ethernet, Modbus ASCII & RTU RS-232/422/485
  • Modbus Flexibility – Serial & Ethernet, Masters & Slaves
  • View Messaging Status in Real Time
  • Ultra Compact IP30 Metal Enclosure
  • International Power Supply (included )

Models MESP211D and MESP211T, Vlinx™ series Modbus Gateways, connect Modbus devices to Ethernet networks and let you monitor and control Modbus devices from anywhere on the Ethernet LAN or WAN. Supporting up to 16 masters and 32 slaves, these gateways feature an auto-detecting 10/100 Ethernet copper RJ-45 port and a serial port that supports RS-232/422/485 communications via a DB9 male or a terminal block connection.

The product is built for use in industrial environments with a heavy-duty metal enclosure that is panel (standard) or DIN rail mountable (with optional adapters). The product can be supplied with a DC power source ranging from 10 to 30 VDC and features a barrel connector. A power supply is included.


Ease of Use

Configuration, upgrades and monitoring of the serial server are simple, easy tasks with Vlinx Manager Software. It installs on your PC giving access to the serial server via your desktop. Remotely manage the Modbus Gateway over a LAN or WAN via the build-in web server. This is helpful for off-site troubleshooting and can be done with an ordinary web browser.


Software Support

Windows XP (32/64 bit), 2003 Server (32/64 bit), Vista 32/64 bit), 2008 Server (32/64 bit), Windows 7 (32/64 bit), Windows 8 (32/64 bit), Windows 10 (32/64 bit).

SPECIFICATIONS

SERIAL TECHNOLOGY
RS-232 (DB9) TD, RD, DTR, DSR, RTS, CTS, DCD
plus Signal Ground
RS-485 2-Wire Data A(-), Data B(+), GND
RS-422/485 4-Wire TDA(-), TDB(+), RDA(-), RDB(+), GND
Serial Protocols & Connectors
MESP211D:
MESP211T:

RS-232/422/485 (DB9 male)
RS-232/422/485 (removeable terminal block)
Data Rate Up to 230.4 Kbps
POWER
Source Power supply, included
Input Voltage 10 to 30 VDC
Power Connector Dimensions 5.5 x 2.1 mm
Power Consumption 2.5 Watts, maximum
POWER SUPPLY (INCLUDED)
Input Voltage 90 to 264 VAC
Frequency 47 to 63 Hz
Power Consumption No load; Level VI = 0.1W; ErP Tier 1 = 0.075W
Operating Temperature 0 to +40 °C
Storage Temperature -10 to +70 °C
Operating Humidity 20 to 80%
Storage Humidity 10 to 90%
Internation Blade Kit North America, Europe, U.K., Australia, China, Japan
MECHANICAL
LED Indicators Serial Port, Ethernet, Ready
Switches Reset Button
Dimensions 7.938 x 5.257 x 2.209 cm (3.125 x 2.070 x 0.870 in)
Enclosure Metal, IP 30
ENVIRONMENTAL
Operating Temperature -40 to +80 °C (-40 to +176 °F)
Operating Humidity 10 to 95% Non-condensing
MEANTIME BEFORE FAILURE (MTBF)
MTBF MESP211D: 997311 hours
MESP211T: 1020400 hours
MTBF Calculation Method MIL 217 F Parts Count Reliability Prediction
NETWORK
Serial Memory 8 KB per port
Network Memory 4 KB
LAN 10/100 Mbps auto-detecting, 10BaseT or 100BaseTX
Ethernet IEEE 802.3 auto-detecting & auto MDI/MDI-X, 10BaseT and 100Base TX
PROTOCOLS
Protocols TCP, IPv4, UDP, ARP, HTTP 1.0, ICMP/PING, DHCP/BOOTP
IP Mode Static, DHCP
TCP/UDP
UDP
User definable
Unicast or Multicast
OTHER
Connection Mode Server, Client, VCOM, Paired
Client Connection At power up or upon data arrival
Search Serial direct COM and Ethernet Auto Search or specific IP
Diagnostics Display PC IP, ping, test VCOM
Firmware Upgrade via Vlinx™ Manager
CONFIGURATION SOFTWARE
Vlinx™ Manager Windows XP (32/64), 2003 Server (32/64), Vista (32/64),
2008 Server (32/64), 7 (32/64), 8/8.1 (32/64), 10 (32/64)
REGULATORY / CERTIFICATIONS / SAFETY
Compliance FCC Part 15 Class B
EMC 2004/108/EC, Electromagnetic Compatibility Directive
2011/65/EU, Reduction of Hazardous Substances Directive
EN55022:+AC, Information Technology Equipment - Class B RF Emissions
EN55024:, Information Technology Equipment - Immunity (Light Industrial Environments)
EN61000-4-2 ESD Immunity
EN61000-4-3:+A2:, Radiated Field Immunity (RFI)
EN61000-4-4:, EFT/Burst Immunity
EN61000-4-5:, Electrial Surges Immunity
EN61000-4-6:, RF Conducted Immunity




ORDERING INFORMATION

Available Modules
BB-MESP211D Ultra Compact Modbus Gateway - RS232/422/485, DB9/RJ45
BB-MESP211T Ultra Compact Modbus Gateway - RS232/422/485, Terminal Block/RJ45




ACCESSORIES

    BB-SMI6-12-V-P5        - Included Power Supply, 12 VDC 6 Watt, 5MM Plug, International AC Input, International AC Blades
    BB-DRAD35 - Optional DIN rail adapter clip (pair)
    BB-232NM9 - Optional mull modem crossover cable

Kunden, die diesen Artikel gesehen haben, sahen auch
Alle Cookies akzeptieren Ablehnen Konfigurieren

Diese Website verwendet Cookies, um eine bestmögliche Erfahrung bieten zu können. Mehr erfahren.