MOXA ioLogik E2262

Smart Ethernet remote I/O with Click&Go, 8 TCs, and 4 DOs

MOXA ioLogik E2262
4250_12598.png
4250_8583.png
  • EigenschaftenEigenschaften
  • BeschreibungBeschreibung
  • Weitere InformationenWeitere Informationen
  • PDFPDF
  • Active communication with patented MX-AOPC UA Server and Active OPC server
  • Smart alarm management with email, SNMP traps, TCP, UDP
  • Save time and wiring costs with peer-to-peer communication
  • Front-end intelligence with patented Click&Go control logic, up to 24 rules
  • Simplify I/O management with MXIO library for Windows or Linux
  • Web browser configurations over HTTP
  • Supports SNMP v1/2c/3
  • Wide operating temperature range of -40 to 75°C (-40 to 167°F)
Die ioLogik E2262 kann die Länge von Sensorleitungen maximal um den Faktor 10 erweitern. Ein Beispiel: Während die Verkabelung für einen J-Typ in der Regel nur 10 m lang sein darf, können Sie die TC-Verkabelung des J-Typs mit dem ioLogik E2262 auf bis zu 100 m ausdehnen.

Genauere Temperaturwerte

Die ioLogik E2262 verfügt über zwei CJC-Klemmen zur Kaltstellenkompensation und unterstützt digitale Filterung. Kalibrierung, Linearisierung und Berechnung basieren auf den vom NIST (National Institute of Standards and Technology) verfolgten Geräten und werden im Speicher abgelegt, um diese Fehlerquelle zu eliminieren. Der ioLogik E2262 kann auch ein Ausbrennen und Unterbrechungen erkennen.

ProdGrafik
Moxa’s ioLogik E2200 is a new type of Ethernet micro RTU controller, which is a PC-based data acquisition and control device that uses proactive, event-based reporting to control I/O devices. Unlike traditional RTUs, which are passive and must poll for data, Moxa’s ioLogik E2200 series with Active OPC Server makes seamless connection with SCADA systems a reality. In addition, SNMP is used for communicating with an NMS (Network Management System) for IT field users. The I/O status of an Ethernet micro RTU controller can be reported and controlled automatically on-site based on user specified conditions. This report-by-exception approach, which is new to PC-based monitoring, requires far less bandwidth than traditional polling methods.

Actice Alarming with Local Intelligence
The ioLogik E2200 Micro RTU supports simple and powerful Click&Go™ technology to deliver event-driven reports and allow alarm messages to be sent by email, TCP/UDP, and SMNP Trap with real-time stamps. With built-in Click&Go™ intelligence, the ioLogik E2200 micro RTU can be used for simple output control when it is triggered by input status, without the need for a PC controller. The ioLogik E2200 micro RTU reports I/O status automatically based on user-specified conditions. This report by-exception approach requires far less bandwidth than the traditional polling approach.


ioLogik E2262 Specifications


Inputs and Outputs

Thermocouple Inputs
8 channels

Digital Outputs
4 channels


Thermocouple Input

Sensor Type
J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C)

Millivolt Type
  • Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
  • Fault and over-voltage protection: -35 to +35 VDC (power off);
    -25 to +30 VDC (power on)

Sampling Rate
12 samples/sec (all channels)

Resolution
16 bits

Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C

Input Impedance
1 M ohms


Digital Output

Type
Sink

I/O Mode
DO or Pulse Output

Pulse Output Frequency
100 Hz

Over-voltage Protection
45 VDC

Over-current Protection
2.6 A (4 channels @ 650 mA)

Over-temperature Shutdown
175°C

Current Rating
200 mA per channel

Isolation
3k VDC or 2k Vrms


Power Requirements

Power Consumption
160 mA @ 24 VDC


MTBF (mean time between failures)

Time
341,063 hrs

Database
Telcordia (Bellcore)



Common Specifications


LAN

Ethernet
1 10/100 Mbps RJ45 port

Protection
1.5 kV magnetic isolation

Protocols
Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP


Serial Communication

Interface
RS-485-2w: Data+, Data-, GND (3-contact terminal block)

Serial Line Protection
15 kV ESD for all signals


Serial Communication Parameters

Parity
None

Data Bits
8

Stop Bits
1

Flow Control
None

Baudrate
1200 to 115200 bps

Protocol
Modbus/RTU


Power Requirements

Power Input
24 VDC nominal, 12 to 36 VDC


Physical Characteristics

Wiring
I/O cable max. 14 AWG

Dimensions
115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)

Weight
under 250 g

Mounting
DIN rail or wall


Environmental Limits

Operating Temperature
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature
-40 to 85°C (-40 to 185°F)

Ambient Relative Humidity
5 to 95% (non-condensing)

Altitude
Up to 2000 m

Note Please contact us if you require products guaranteed to function properly at higher altitudes.


Standards and Certifications

Safety
UL 508

EMI
EN 61000-3-2; EN 61000-3-3; EN 61000-6-4;

FCC
Part 15, Subpart B, Class A

EMS
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61000-6-2

Shock
IEC 60068-2-27

Freefall
IEC 60068-2-32

Vibration
IEC 60068-2-6

Green Product
RoHS, CRoHS, WEEE



Ordering Information

Available Modules
ioLogik E2262 Ethernet Micro RTU Controller with 8 thermocouple inputs and 4 digital outputs
ioLogik E2262-T Ethernet Micro RTU Controller with 8 thermocouple inputs and 4 digital outputs,
-40 to 85°C operating temperature

Kunden, die diesen Artikel gesehen haben, sahen auch
Alle Cookies akzeptieren Ablehnen Konfigurieren

Diese Website verwendet Cookies, um eine bestmögliche Erfahrung bieten zu können. Mehr erfahren.